Two Supplies, One Decision — Intelligent Mains-Mains / Mains-Generator Switching

The EXUR7P-2 is a DIN-rail automatic transfer switch (ATS) for dual power systems up to 100A, supporting mains-to-mains and mains-to-generator changeover. Two physically isolated inputs feed one load through a microcontroller-based switch that checks voltage quality, applies over/under voltage and overcurrent protection, offers phase priority selection, timing functions, and WiFi monitoring — restoring supply automatically when the preferred source recovers.

النموذج


EXUR7P-2 Series — ATS with Overvoltage & Undervoltage ProtectorEXUR7P-2 (63A / 80A / 100A)

طلب عرض سعر جملة

AC 2×110/220V · 63-100A · dual isolation · WiFi app

Mains + Generator Switching
Physical Input Isolation
0.5-Class Metering

تفاصيل المنتج

  • Dual-power ATS for mains-mains or mains-generator changeover, rated 63/80/100A.
  • Physically isolated inputs prevent back-feeding; priority selection L1/L2 or ATO mode.
  • Over/under voltage, overcurrent and temperature protection with delayed restart after recovery.
  • Timer for scheduled on/off; 0.5-class metering; WiFi monitoring; DIN rail mounting.
إرسال استفسار

معلومات المنتج

  • تفاصيل المنتج
  • التنزيلات
  • استفسار

General

The EXUR7P-2 series products are applicable to rated currents of 100A and below, supporting intelligent switching between dual power supplies of mains-to-mains and mains-to-generator. The two input circuits adopt a physical isolation design, fully complying with electrical safety specifications and standards.

It features dual modes of automatic circuit switching and manual free switching for flexible and convenient use. The overvoltage and undervoltage protection thresholds can be customized; automatic power-off protection is triggered immediately when the voltage exceeds the set range. A built-in delayed restart mechanism enables automatic closing and power supply restoration after the grid voltage stabilizes. Meanwhile, it allows independent setting of the current limiting value, with automatic power-off upon overcurrent and self-recovery after fault elimination.

The complete machine integrates multiple safety protections including neutral loss, overvoltage, undervoltage and overload,comprehensively preventing hidden risks such as grid voltage fluctuations and current abnormalities. It effectively ensures the long-term stable operation of rear-end electrical equipment and avoids fault damage.

Operating Conditions

  • When installing the product, the input terminal must be connected to a circuit breaker.
  • After receiving the product, first connect only one power source to check if the display is normal.
  • The equipment must be installed by qualified professionals.
  • Before operating the device, disconnect all power supplies and do not touch any terminal when the power supply is connected.
  • Verify that terminals are properly connected.
  • Do not use the equipment in places that may be corroded by gas, strong sunlight and rain.
  • Clean equipment with a dry cloth.
  • Failure to comply with these instructions will result in serious injury or serious accident

الميزة

  • Automatic Transfer Switch: with “priority” phase
  • Microcontroller-based
  • Digital display of working voltage, current
  • Measurement accuracy is 0.5 class
  • Key setting parameter
  • Can set the priority phase sequence
  • تركيب على سكة DIN

البيانات الفنية

Rated supply voltage AC 2*110V/220V
Operating voltage range AC 80-300V
Rated frequency 50/60Hz
Hysteresis Overvoltage:5V;Undervoltage:5V
Measurement accuracy 0.5 class
Rated insulation voltage 450V
Output contact 1NO
Electrical life 10⁵
Switch delay to reserve phases >0.2s
Overvoltage trip delay 0.1s;≥350V;0.02s
Undervoltage trip delay 0.1s;≥350V;0.02s
Mechanical life 10⁶
Protection class IP20
درجة التلوث 3
الارتفاع <2000m
درجة حرارة التشغيل -5℃~40℃
الرطوبة ≤50%or40℃
Storage temperature -10℃~55℃
Product size 63A:90*96*67mm;80A/100A:90*103*67mm
Voltage accuracy <1%
Rated operating current 63A/80A/100A
Max.operating current 63A/100A

Display Panel

EXUR7P-2 Display Panel

Electrical Symbol Diagram

EXUR7P-2 Electrical Symbol Diagram

Wiring Diagram

EXUR7P-2 Wiring Diagram

Program Description

Set character Technical parameter Set range Default value Step forward Function description
P-1 Power-on delay time 1s-999s 5s 1s After external power cut,the time needed for

power-on when power recovery.

P-2 Recovery/Switch Time 1s-999s 10s 1s Is the time required for the line to return to normal
or switch to a working line.
P-3 Timed off OFF-0.1m-999m OFF 0.1m Can be used to time off the device
P-4 Timed   on ON-0.1m-999m ON 0.1m The P-3 timer off parameters must be changed
before the timer on parameters can be adjusted.
P-5 Input phase priority

selection

L1-L2-ATO L1 1 Operating mode:When L1 or L2 is selected,it’s a
priority phase selection;ATO:Non-priority mode,
fixed to the current phase.
P-6 Over-voltage
protection value
120V-300V
-OFF
270V    140V 1V When the voltage of one phase is over the set
value,the protector will cut off this phase and switch to
the next phase according to the sequence set
in P5.When all voltage is over the set value,the
protector will cut off all lines.
P-7 Under-voltage
protection value
OFF-80V-210V 170V90V 1V When the voltage of one phase is under the set value,
the protector will cut off this phase and switch to the
next phase according to the sequence set
in P5.When all voltage is under the set value,the
protector will cut off all lines.
P-8 Voltage calibration ±9.9% 0 0.10% Correct the voltage error.
P-9      Over-current
protection value
1A-63A/100A-

OFF

63A   80A 1A When the current is higher than the set value,
the protector will cut off the line.When setting
OFF,the protector will turn off over-current
protection function.
P-10 Current calibration ±9.9% 0 0.10% Calibrate current current value
P-11 Overcurrent
حماية
action time
0.1s-30s 1s 0.1s When over current,the time needed for
protection action.
P-12 Times of continuous

over current
حماية

OFF-1-20 OFF 1 When the times of continuous over-current protection
exceeds the set value,the protector will cut off the line,
then it needs to be opened manually.
P-13 Temperature

حماية

40℃-120℃ 90℃ 1℃ After temperature protection,the hysteresis
value is restored to 10℃.

Setup Menu

EXUR7P-2 Setup Menu

Fault Description

EXUR7P-2 Fault Description

Overall and Mounting Dimensions (mm)

EXUR7P-2 Overall and Mounting Dimensions (mm)

كيف ندعم عملك

EXUR7P-2 OEM ATS customization for genset manufacturers

الشركة المصنعة الأصلية / التصميم والتصنيع حسب الطلب

تعرف على المزيد →

Pre-set priority schemes, custom faceplates and wiring labels for generator-set and panel OEMs.


Priority presets · Custom faceplates · Test records

EXUR7P-2 automatic transfer switches wholesale

Factory-direct pricing for distributors supplying backup-power and dual-supply solutions to commercial and industrial customers.


تسعير المصنع · حد أدنى للطلب مرن · شحن عالمي

EXUR7P-2 distributor technical support ATS

دعم الموزعين

تعرف على المزيد →

Application guides, wiring documentation and priority production for partners in the standby power market.


Application guides · Wiring docs · Priority lead times

Ready to Stock the EXUR7P-2 Series?

OEM/ODM, wholesale pricing and distributor support — one enquiry gets you a factory-direct quotation for automatic transfer switches in 63A, 80A and 100A, configured for your mains and generator scheme.

اتصل بفريق المبيعات لدينا

الأسئلة الشائعة

What is an automatic transfer switch (ATS) and when is it used?

An ATS connects a load to two power sources and automatically transfers the load from the preferred source to the standby source when the first fails, then back when it recovers. The EXUR7P-2 is used with two mains feeders or a mains/generator pair in houses, shops, telecom shelters and small commercial plants that need continuity of supply without someone driving to the site to throw a changeover switch.

What is the difference between mains-mains and mains-generator operation?

Mains-mains connects two utility feeders where either can carry the load; the ATS selects by priority. Mains-generator connects the utility and a standby generator, typically with the generator started by an external controller — the ATS transfers when the grid fails and returns when it stabilises. The EXUR7P-2 supports both topologies with physically isolated inputs.

Why must each input have a circuit breaker?

The installation instructions require a breaker on the input side of the ATS. This protects the wiring and the device during fault conditions, and — critically — provides a guaranteed point of isolation for maintenance. The ATS itself provides protection functions, but it cannot replace upstream overcurrent protection.

How does the EXUR7P-2 choose which source to use?

You set the priority in the menu: L1 priority or L2 priority makes one input the preferred source that is used whenever its voltage is healthy; ATO (automatic) is a non-priority mode that stays on the current source until it fails. When the preferred source fails, the ATS checks the standby source and transfers after a minimum delay of 0.2 seconds.

What protections are built into the EXUR7P-2?

The unit combines overvoltage and undervoltage protection (with fast trip ≤350V in 0.02s), overcurrent protection with adjustable limits and an action delay, temperature protection (40-120°C), neutral-loss protection and overload safeguards. After a fault or outage it reconnects after the configured recovery delay so the load returns to a stable supply.