Beranda > Produk > Semua Produk > EXUR7-3 Protektor Tegangan Lebih dan Tegangan Kurang

EXUR7-3 Protektor Tegangan Lebih dan Tegangan Kurang

Pelindung Tiga Fasa — Proteksi Over, Under, Ketidakseimbangan dan Urutan Fasa

EXUR7-3 adalah perangkat proteksi jalur tiga fasa berkinerja tinggi yang secara terus-menerus memantau tegangan RMS dan arus dari ketiga fasa dan memutus beban pada kondisi overvoltage, undervoltage, overcurrent, kesalahan urutan fasa atau ketidakseimbangan tiga fasa. Dapat dikonfigurasi untuk sistem AC220V tiga fasa empat kawat atau AC380V tiga fasa tiga kawat, dengan rating 63A, 80A, dan 100A, serta reset otomatis setelah gangguan teratasi.

EXCB1-DC2-1


Seri EXUR7-3 — Pelindung Tegangan Over/Under Tiga FasaEXUR7-3□□ (63A / 80A / 100A; 220V 3P4W atau 380V 3P3W)

Minta Penawaran Grosir

AC220V (L-N) / AC380V (L-L) · urutan fasa + ketidakseimbangan · reset otomatis

Proteksi Urutan Fasa
Deteksi Ketidakseimbangan
Rentang Arus 1-100A

Detail Produk

  • Proteksi tegangan over/under dan overcurrent tiga fasa dengan pemantauan RMS per fasa.
  • Proteksi urutan fasa dan proteksi ketidakseimbangan tiga fasa yang dapat disesuaikan (20-100V).
  • Dik konfigurasi untuk AC220V tiga fasa empat kawat (L-N) atau AC380V tiga fasa tiga kawat (L-L); 63/80/100A.
  • Reset otomatis dengan delay yang dapat dikonfigurasi; tampilan digital; kontak output 1NO; IP20.
Kirim Pertanyaan

Informasi Produk

  • Detail Produk
  • Unduhan
  • Pertanyaan

Umum

EXUR7-3 adalah perangkat proteksi jalur tiga fasa berkinerja tinggi. Perangkat ini secara terus-menerus memantau nilai efektif tegangan dan arus tiga fasa, dan dapat dengan cepat memutus sirkuit saat terdeteksi gangguan overvoltage atau undervoltage yang telah diprogram, secara efektif mencegah kerusakan peralatan listrik dan kecelakaan keselamatan yang disebabkan oleh abnormalitas jaringan listrik atau kerusakan peralatan. Setelah gangguan teratasi, perangkat mendukung reset otomatis untuk mengembalikan pasokan listrik.

Fitur

Relay tampilan tegangan dan arus yang digunakan di gedung administratif, industri, dan residensial serta memiliki fungsi melindungi jalur satu fasa:

  • Bekerja dalam mode voltmeter;
  • Proteksi undervoltage;
  • Proteksi overvoltage;
  • Proteksi overcurrent.
  • Proteksi urutan fasa;
  • Proteksi ketidakseimbangan tiga fasa;

Data Teknis

Item AC220V (Tiga fasa empat kawat) AC380V (Tiga fasa tiga kawat)
Tegangan suplai terukur Tegangan Fasa AC220V (L-N) Tegangan Jalur AC380V (L-L)
Rentang tegangan operasi AC80_400V (Tiga fasa) AC140-400V (Tiga fasa)
Frekuensi terukur 50/60Hz 50/60Hz
Rentang pengaturan arus listrik 1-100A 1-100A
Rentang pengaturan tegangan over 120-300V (220V) 400-520V (380V)
Rentang pengaturan tegangan under 80-210V (220V) 140-360V (380V)
Arus terukur 63A/80A/100A 63A/80A/100A
Delay trip U 1-10s 1-10s
Delay reset/start 1-999s 1-999s
Akurasi pengukuran tegangan ±2% ±2%
Tegangan isolasi terukur 400V 700V
Kontak output 1NO 1NO
Electrical life 10⁵ 10⁵
Mechanical life 10⁶ 10⁶
Derajat perlindungan IP20 IP20
Derajat polusi 3 3
Ketinggian ≤2000m ≤2000m
Suhu operasi -5℃~+55℃ -5℃~+55℃
Kelembaban ≤50%at 40℃(without condensation) ≤50%at 40℃(without condensation)
Storage temperature -30℃~+70℃ -30℃~+70℃

Default Setting

Technical parameter Setting range Step Factory setting
Power-on delay time 1-999s 1s 5s
Over-voltage protection value 120-300V/400-520V 1V 270V/430V
Over-voltage recovery value 115-295V/395-515V 1V 265V/425V
Over-voltage recovery delay time 1-999s 1s 30s
Over-voltage protection action time 1-10s 0.1s 0.5s
Under-voltage protection value 80-210V/140-360V 1V 170V/300V
Under-voltage recovery value 85-215V/145-365V 1V 175V/315V
Under-voltage recovery delay time 1-999s 1s 30s
Under-voltage protection action time 1-10s 0.1s 0.5s
Three-phase voltage error value -9.5V~9.5V 0.5V 0
Three-phase voltage unbalance value 20-100V 1V 50V
Three-phase voltage unbalance protection switch OFF/ON ON
Phase sequence protection OFF/ON ON
Over-current protection value 1-63A/80A/100A 1A 100A
Over-current recovery delay time 1-999s 1s 30s
Over-current protection action time 1-10s 0.1s 0.5s
Three-phase current error -9.5A~9.5A 0.5V 0
Continuous over-current protection times 0-20/OFF 1 OFF

Setup Menu

EXUR7-3 Setup Menu

Display Panel

EXUR7-3 Display Panel

Reset / Start Delay Display

Reset Start Delay Display

Voltage operating values are shown on L1-L2-L3 and on current during the start of delay counting on L2 Value display; After the delay is over, the output relays close and they will open normally.

Phase Sequence Error Indication

Phase Sequence Error Indication

When a phase fault occurs, L1-L3-L2 is displayed, and the protectoris disconnected from the output power supply.

Indication of Continuous Over Current Faults

Indication of Continuous Over Current Faults

Continuous over current fault indicationDisconnect overload deviceStart the relay after manual reset.

Electrical Symbol

Product Status Description

  • If a voltage fault is detected during the reset/start-up delay period, the output relay will energize and the fault indicator will light up.
  • During normal operation, the screen displays the operating voltage and current values; if a voltage or current fault is detected, the output relay energizes and the fault indicator lights up.
  • Voltage Fault: After a voltage fault occurs, if the input voltage is detected to have returned to within the hysteresis (Hys) range, the relay will automatically reset once the reset/start-up delay period concludes; the fault indicator will turn off, and the screen will display the operating voltage and current values.
  • Current Fault: When the relay trips due to a current fault, it will automatically reset; during the reset/start-up delay period, the fault indicator turns off, and the screen displays the operating voltage and current values.

Electrical Symbol

Wiring Diagram

The wiring diagram is for reference only; please refer to the actual wiring.

EXUR7-3 Wiring Diagram

Overall and mounting dimensions (mm)

Overall and mounting dimensions (mm)

Bagaimana Kami Mendukung Bisnis Anda

EXUR7-3 OEM three phase protector customization

Pre-set thresholds and 220V/380V defaults with custom faceplates for machine and panel OEMs.


Market presets · Custom faceplates · Calibration data

EXUR7-3 three phase voltage protectors wholesale

Factory-direct pricing for distributors serving industrial, agricultural and commercial three-phase customers.


Harga pabrik · MOQ fleksibel · Pengiriman global

EXUR7-3 distributor technical support

Dukungan Distributor

Pelajari lebih lanjut →

Wiring-scheme guides, threshold tables and priority production for partners in the motor protection market.


Wiring guides · Threshold tables · Priority lead times

Ready to Stock the EXUR7-3 Series?

OEM/ODM, wholesale pricing and distributor support — one enquiry gets you a factory-direct quotation for three-phase voltage protectors in 63A, 80A and 100A, configured for your 220V or 380V system.

Hubungi Tim Penjualan Kami

Pertanyaan yang Sering Diajukan

What is a three-phase voltage protector and what does it protect against?

A three-phase voltage protector monitors the three phases of a supply as a group and disconnects the load when the supply is unhealthy. The EXUR7-3 protects against overvoltage, undervoltage and overcurrent on any phase, incorrect phase sequence, and voltage unbalance between phases — the five fault classes that cause motor burnout, machine damage and control failure in three-phase installations.

Why is phase sequence protection important?

If two phases are swapped at commissioning or after maintenance, a three-phase motor reverses direction — dangerous for pumps, compressors and conveyors, and capable of destroying them. Phase-sequence protection verifies the order of L1-L2-L3 before closing the output and disconnects the load if the sequence is wrong, displaying the fault for the electrician.

What is three-phase voltage unbalance and when should I set it?

Unbalance is the difference between the highest and lowest phase voltages. Motor standards commonly warn that unbalance above 2-3% raises winding temperature significantly; the protector compares phase voltages and trips when the difference exceeds the user setting (20-100V). On a nominal 380V system a 50V default is permissive; set lower for sensitive motors.

Does the EXUR7-3 work on a 220V three-phase system?

Yes. Select the three-phase four-wire mode where phase voltage is 220V L-N (e.g. 380/220V four-wire networks), and the threshold tables automatically present the 220V-range settings (overvoltage 120-300V, undervoltage 80-210V). In three-wire 380V systems the device reads line-to-line and applies the 380V tables.

How does the EXUR7-3 reset after a fault?

After the fault clears and the line returns to the healthy window for the configured recovery delay, the output relay closes again automatically. If the continuous overcurrent count reaches its user limit (0-20), the device locks out and requires a manual reset — a deliberate behaviour that flags repeated overloads rather than endlessly re-closing onto a faulty load.