HYGLDC Load Isolation Switch 1000V/1500V DC for PV Systems

HYGLDC series high-voltage DC isolator switch rated 160-1000A, 1000V/1500V DC. 12kV impulse withstand, 10kA short-time withstand (0.1s), 10,000 mechanical operations. Ideal for photovoltaic combiner boxes, inverters, and battery storage systems. IEC/UL compliant. OEM/ODM available.

- Suitable for PV system main switches, distribution boxes, and power cabinets.

- Visible contact technology ensures a high level of safety.

- Capable of on-load operation; meets isolation requirements and ensures personal safety

Send Inquiry

Product Information

  • Product Details
  • Downloads
  • Inquiry

Technical Parameters

Model 250 250G 325G 400 630 800 1000
Rated operational current le(A) 160/200/250 160/200/250 275/300/325 315/400 500/630 700/800 1000
Rated insulation voltage Ui(V) 1000
Pollution Level 3
1500
Pollution Level 2
1500
Pollution Level 2
1500
Pollution Level 2
1500
Pollution Level 2
1500
Pollution Level 2
1500
Pollution Level 2
Rated impulse withstand voltage (kV) 12 12 12 12 12 12 12
Rated thermal current Ith(free air)(A) 160/200/250 160/200/250 275/300/325 315/400 500/630 700/800 1000
Cable or busbar cross-section(Copper/Cu)(mm²) 70/95/120 70/95/120 185/185/185 185/240 2×240 2×240 4×150
Rated short-time withstand current Icw(kA) 5(1s),10(0.1s) 10(0.1s) 10(0.1s) 10(0.1s) 10(0.1s) 10(0.1s) 10(0.1s)
Rated short-circuit making capacity lcm(peak)(kA) 10 10 10 10 10 10
Terminal screw specifications(diameter×length)(mm) M8×25 M8×25 M8×25 M10×30 M10×30 M10×30 M10×30
Terminal tightening torque (locking torque)(Nm) 15-22 15-22 15-22 30-44 30-44 30-44 30-44
Mechanical life (number of operations) 10000 10000 10000 10000 10000 10000
Operating altitude(without derating)(m) ≤2000 ≤2000 ≤2000 ≤2000 ≤2000 ≤2000

Appearance and Dimensions

Model A B C D E F G H I J K L P
HYGLDC-250 144 168 190 70 115.5 20 10.5 35 70 76 325.5 24 35
HYGLDC-250G/325G 133 142 165 76 149 197 9 39 77 109.5 314.5 25 39
HYGLDC-400/630 164 184 211 124.5 171 30 13 49 101 125 419.5 31 49
HYGLDC-800/1000 164 184 211 124.5 171 30 13 49 101 125 419.5 31 49

Model Q R S T U V W
HYGLDC-250 100 102 86 169 122 119 105
HYGLDC-250G/325G 125.5 110 111.5 178 116 114 100
HYGLDC-400/630 155 188 138 219 167 163 149
HYGLDC-800/1000 155 188 138 219 167 163 149


Model M N
HYGLDC-250F11K 125 87
HYGLDC-250F22K 185 157
HYGLDC-325GF11K 126 96
HYGLDC-325GF22K 199 175
HYGLDC-630F11K 225 132
HYGLDC-630F22K 274 230
HYGLDC-1000F11K 225 132
HYGLDC-1000F22K 274 230

Model Q R S T U V W
HYGLDC-250F11K 137 87
HYGLDC-250F22K 185 157
HYGLDC-325GF11K 138 98
HYGLDC-325GF22K 199 176
HYGLDC-630F11K 205 132
HYGLDC-630F22K 259 230
HYGLDC-1000F11K 205 132
HYGLDC-1000F22K 259 230

Frequently Asked Questions

What does an isolation switch do?

An isolation switch (also known as a disconnect switch) allows the direct cutting of the circuit and separating the electrical installations from the power supply for the purpose of safe maintenance. It is constructed in such a way that it does not break the electric current as it is used for safe disconnection of the circuit. Our HYGLDC series DC isolation switches are suitable for voltages of 1000V/1500V DC and currents from 160 to 1000A, providing a reliable visual isolation for photovoltaic systems and energy storage plants.

What is the difference between a load break switch and an isolation switch?

The load break switch has been designed for the purpose of safely making and breaking electricity. In contrast to a load break switch, the isolation switch is not designed for breaking load current, only for isolation when the current is already off. Isolation switches give a visible air gap while performing maintenance. The HYGLDC series is an isolation switch primarily for DC circuits where it is used as a disconnect switch in combiner boxes and inverter DC inputs.

Is isolator on load or off load?

The isolation switch, or isolator, is made to operate off-load, so its circuit must be interrupted when the switch is open or closed. The HYGLDC series makes it possible to see when a PV or battery DC circuit is isolated. With a mechanical life of 10,000 operations and a short-time withstand current of 10kA (0.1s), it guarantees safe operation of an off-load switch.

Should the isolation switch be on or off?

In regular functioning, the isolation switch ought to be in the ON position (so that the current flows) while it must be OFF during maintenance, repair, and unforeseen circumstances (thus, disconnecting the machinery from electricity). When it is OFF, the switch creates the visible interruption of electricity; thus, it assures that there is no electric connection in line with safety requirements for lockout/tagout (LOTO) practices. The HYGLDC range from our company guarantees the visible indication of its state thus allowing safe operation of solar PV systems and storage batteries.