Home > Product > All Product > EXC7 AC Contactor

EXC7 AC Contactor

One Contactor Family from 9A to 800A — Motor, HVAC & Power Switching

The EXC7 AC contactor family spans standard contactors from 9A to 110A and high-current frames from 120A to 800A, all in 3P with a 690V insulation class (1000V on large frames). Standard models feature wide-voltage tolerance and full dust protection; high-current frames use a dual-coil control circuit that cuts holding power by more than 40%, plus built-in 2NO+2NC auxiliary contacts.

Model

✓
EXC7 Series — AC Contactor & High-Current AC ContactorEXC7-09 ~ EXC7-110 · EXC7-120 ~ EXC7-800 (frames 120/160/185/225/265/330/400/500/630/800)

Request a Wholesale Quotation

IEC 60947-4-1 · CE approved · 690V / 1000V insulation · dual-coil large frames

9A to 800A Coverage
Dual-Coil Energy Saving
2NO+2NC Standard (large)

Product Details

  • One contactor family from 9A to 110A (standard) and 120A to 800A (high-current frames), all 3P.
  • Ui 690V (standard) / 1000V (high-current); switches motors from 4kW up to 450kW at 400V.
  • High-current frames use a dual-coil circuit that cuts holding power by over 40% and include 2NO+2NC auxiliary contacts as standard.
  • Full accessory system — auxiliary blocks, pneumatic delay heads, surge suppressors, interlocks, dust covers; IEC 60947-4-1; CE.
Send Inquiry

Product Information

  • Product Details
  • Downloads
  • Inquiry

Three Key Features

  • More auxiliaƔ contacts come as standard, meeting diverse application requirements
  • Suitable for wider voltage Əuctuations, ensuring stable operation of the equipment
  • Superior environmental adaptability, enabling reliable operation even in extreme conditions

Product Structural Analysis Diagram

EXC7 Product Structural Analysis Diagram

Product Overview

The all-new EXC7 series AC contactors feature a novel design and a compact structure.This series is primarily used for the frequent starting and control of AC motors and for remote circuit switching; it can also be combined with a suitable thermal overload relay to form an electromagnetic staƑer.

Compliant with standards: IEC60947-1, IEC60947-4-1.

Main Technical Parameters

  • Rated workingcurrent:9-95A;
  • Rated workingvoltage:220Vto 69OV;
  • Rated insulation voltage: 690V;
  • Polarities:3P
  • Installation method: rail and screw

Working Conditions and Installation Conditions

Category Working conditions and installation conditions
Installation category Ⅲ
Pollution degree 3
Certification mark CE
Enclosure protection class CJX2s-09~38:IP20(excluding terminals)
CJX2s-40~95:IP10;CJX2s-110:IP00
Ambient air temperature Extreme operating temperature:-35℃ to+70℃;
Normal operating temperature:-5℃ to +40℃;Average temperature over a 24-hour period:not exceeding+35℃.For use outside the normal operating temperature range,
please refer to the “Instructions for Use in Non-standard Environments.”
Altitude Not exceeding 2000m
Ambient air temperature At a maximum temperature of+70℃,relative humidity shall not exceed 50%;

higher relative humidity is permissible at lower temperatures,

e.g.,up to 90%at+20℃.

Special measures should be taken regarding occasional condensation caused by temperature fluctuations.

Installation conditions Inclination of the mounting surface relative to the vertical plane:not exceeding±5°
Shock and vibration The product should be installed and used in locations free from significant swaying,shock,and vibration.

Instructions for Use in Extreme Temperature Environments

  • The GB/T 14048.1 standard speciƍes the normal operating ambient temperature range for the product; performance remains unaffected when the product is used within this range.
  • When the operating ambient temperature exceeds +40°C, the permissible temperature rise limit must be adjusted downward. In such cases, the rated operating current must be reduced, and the number of contactors installed in standard assemblies must be limited; failure to do so may result in product damage, reduced seƒice life, compromised operational reliability, and an impact on the product’s operating range.
  • When the operating ambient temperature falls below -5°C, consideration must be given to the fact that greases used for insulation and lubrication may solidify at low temperatures, potentially causing product malfunction. Therefore, manufacturers and users should consult regarding design or application requirements.
  • The table below lists the derating factors for rated operating current when the rated operating voltage remains constant and the operating ambient temperature exceeds 55°C.
Ambient temperature(℃) 55 60 65 70
Correction Factor 1 0.93 0.875 0.75
  • +55°C to +70°C: The pick-up voltage range for the AC contactor is (90%–110%)Us. The (70%–120%)Us range represents test results obtained under cold-state conditions at an ambient temperature of 20°C.
  • The following table lists the correction factors for rated impulse withstand voltage and rated operating current when the rated operating voltage remains unchanged and the altitude exceeds 2000 m:
Altitude(m) 2000 3000 4000 5000
Correction Factor for Rated Impulse Withstand Voltage 1 0.88 0.78 0.7
Correction Factor for Rated Working Current 1 0.92 0.9 0.85

Features and Performance

Main Technical Parameters
Model(EXC7) -9 -12 -18 -25 -32 -38 -40 -50 -65 -80 -95 -110
Main circuit characteristics
Polar number 3P
Rated insulation voltage(Ui) V 690
Rated operating voltage(Ue) V 380/400,660/690
Agreed heating current(Ith),AC-1 rated operating current 20 25 32 40 50 50 60 80 80 100 125 140
Rated working

current (le)

AC-3,380/400V A 9 12 18 25 32 38 40 50 65 80 95 110
AC-3,660/690V A 6.6 8.9 12 18 22 22 34 39 42 49 49 86
AC-4,380/400V A 3.5 5 7.7 8.5 12 14 18.5 24 28 37 44 51
AC-4,660/690V A 1.5 2 3.8 4.4 7.5 8.9 9 12 14 17.3 21.3 25
Rated working
power(Pe)
AC-3,380/400V kW 4 5.5 7.5 11 15 18.5 18.5 22 30 37 45 55
AC-3,660/690V kW 5.5 7.5 10 15 18.5 18.5 30 37 37 45 45 80
AC-4,380/400V kW 1.5 2.2 3.3 4 5.4 5.5 7.5 11 15 18.5 22 25.5
AC-4,660/690V kW 1.1 1.5 3 3.7 5.5 6 7.5 10 11 15 18.5 21.7
Mechanical life 10,000 times 1200 1000 900 650
Electrical life AC-3 10,000 times 110 90 65
AC-4 10,000 times 22 17 11
Operating

frequency

AC-3 Times per hour 1200 600
AC-4 Times per hour 300 180
The wiring capability of the main circuit terminals
Flexible wire

With terminal blocks

1 wire mm² 1….4 1.…6 2.5…25 4…50 10…150
2 wires mm² 1.….2.5 1..4 2.5.…10 4..16 10…75
Hard wire

No terminal blocks

1 wire mm² 1….4 1.5.….6 1.5…10 2.5.…25 4…50 10…150
2 wires mm² 1.…4 1.5.…6 2.5.…10 4.….25 10…75
Fastening torque N.m 1.2 1.8 6 9 10
Coil
Rated control circuit
voltage(Us)
50Hz V 24、36、48、110、127、220/230、240、380/400、415、440
50/60Hz V 24、36、48、110、127、220/230、240、380/400、415、440
Allowable control
circuit voltage(Us)
Operation V 70%~120%
Release V 20%~65%
Coil power

consumption

Pull-in VA 60 70 200 200
Holding VA ≤9.0 ≤14 ≤25 ≤25
Auxiliary contact
Contact specification A 1NO/1NC
Agreed heating current(Ith) A 10
Rated operating AC V 380
voltage(Ue) SD V 220
Rated control AC-15 VA 360
capacity DC-13 W 33

Shape and Installation Dimensions

CJX2s–09~38

CJX2s-09~38

CJX2s–40~95

CJX2s-40~95

CJX2s–110

CJX2s-110

Model Amax Bmax Cmax Dmax Emax a b C d Φ 1 Φ2
EXC7-09,12,18 74.5 45.5 89 68 119 34 50/60 – 4.5 一
EXC7-25,32,38 83 56.5 100 79 130 40 50/72 一 一 4.5 –
EXC7-40,50,65 127.5 74.5 120 96 150 59 116 40 105 5.5 6.5
EXC7-80,95 127.5 85.5 127 107 157 67 116 40 105 5.5 6.5

CJX2s-09~95+JR28s-25~93

CJX2s-09~95+JR28s-25~93

Model Hmax Imax Jmax
EXC7-09~18 47 122 100
EXC7-25 58 130 107
EXC7-32~38 58 143 96
EXC7-40~65 75 174 125
EXC7-80~95 86 180 128

CJX2s-09N~95N

CJX2s-09N~95N

Model Gmax e
EXC7-09~18 107 95
EXC7-25~38 130 110.5/111.5
EXC7-40~65 164 148
EXC7-80~95 186 166.5

EXC7 High-current AC Contactor

Three Key Features

  • Dual-coil control circuit, compliant with the trend of energy conseƒation and consumption reduction
  • Adaptable to wider voltage Əuctuations, ensuring stable equipment operation
  • Superior environmental adaptability, reliable operation even in extreme conditions

Product Structural Analysis Diagram

EXC7 High-current AC Contactor

Product Overview

The new EXC7-120~80oA series AC contactors feature an innovative appearance and a compact structure. They are mainly used for frequent staƑing and control of AC motors, remote switching on and oƆ of circuits, and can be combined with appropriate thermal overload relays to form electromagnetic starters

Complies with standards: GB/T 14048.1/lEC 60947-1,GB/T 14048.4/lEC 60947-4-1

Main Technical Parameters

  • Rated working current: 120-800A;
  • Rated working voltage: 220V to 690V;
  • Rated insulation voltage: 1000V;
  • Polarities: 3P
  • Installation method: rail and screw

Working Conditions and Installation Conditions

Category Working conditions and installation conditions
Installation category Ⅲ
Pollution degree 3
Enclosure protection class IP00
Ambient air temperature The maximum operating temperature is-35℃ to +70℃,and thenormal operating temperature is

-5℃ to +40℃ The average value within 24 hours does not exceed +35℃.

If used outside the normal operating temperature range,for details,please refer to the “Instructions for

Use in Abnormal Environments”

Altitude No more than 2000m
Ambient air temperature When the maximum temperature is+70℃,the relative humidity of the air shall not exceed 50%.

Higher relative humidity is allowed at lower temperatures For example,it reaches 90%at+20℃.

Special measures should be taken for condensation that occasionally occurs due to changes in humidity

Installation conditions The inclination between the installation surface and the vertical surface shall notexceed+5°.
Shock and vibration The product should be installed and used in a place free from significant shaking,shock and vibration

Instructions for Use in Abnormal Temperature Environments

  • The GB/T 14048.1 standard speciƍes the normal operating ambient temperature for the product.When used within the normal operating ambient temperature range, the product’s peƐormance is not signiƍcantly affected.
  • When the operating ambient temperature exceeds +40°C, it is necessaƔ to consider derating the permissible temperature rise limit. In such cases, the rated operating current must be reduced, and the number of contactors installed in standard assemblies must be decreased. Failure to do so may result in product damage, reduced seƒice life, diminished operational reliability, and an impact on the product’s operating range.
  • When the operating ambient temperature falls below -5°C, consideration must be given to the fact that greases used for insulation and lubrication may solidify at low temperatures, potentially causing product failure. Therefore, the manufacturer and the user should consult regarding design or usage requirements.
  • The table below lists the rated operating current derating factors for instances where the rated operating voltage remains constant but the operating ambient temperature exceeds 55°C.
Ambient temperature(℃) 55 60 65 70
Correction Factor 1 0.93 0.875 0.75
  • +55°C~+70°C: The pull-in voltage range of the AC contactoris(90%~110%)Us.The range of(70% ~120%)Us is the testresult obtained under the condition of cold state atnormaltemperature of 20°C
  • The following table provides correction factors for the rated impulse withstand voltage and rated workingcurrent when the altitude exceeds 20oom with the rated working voltage remains unchanged:
Altitude(m) 2000 3000 4000 5000
Correction Factor for Rated Impulse Withstand Voltage 1 0.88 0.78 0.7
Correction Factor for Rated Working Current 1 0.92 0.9 0.85

Features and Performance

Main Technical Parameters
Frame Size 120 160 185 225 265 330 400 500 630 800
Main circuit characteristics
Polar number 3P
Rated insulation voltage(Ui) V 1000
Rated operating voltage(Ue) V 380/400,660/690
Agreed heating current(Ith),AC-1 rated operating current 200 200 275 275 315 380 450 630 700 900
Rated working
current(le)
AC-3,380/400V A 120 160 185 225 265 330 400 500 630 800
AC-3,660/690V A 86 107 107 118 170 235 303 353 400 470
Rated working
power(Pe)
AC-4,380/400V kW 55 75 90 110 132 160 200 250 335 450
AC-4,660/690V kW 80 100 100 110 160 200 300 335 350 375
Mechanical life 10,000 times 600
Electrical life AC-3 10,000 times 120 80
Operating frequency AC-3 10,000 times 800 600
The wiring capability of the main circuit terminals
Flexible wire

With terminal blocks

1 wire mm² 10.…95 10…150 /
2 wires mm² 10.…95 10…75 /
Hard wire

No terminal blocks

1 wire mm² 10.…95 10.…150 50…240
2 wires mm² 10.…95 10.….75 50.…240
Fastening torque N.m 10 14
Coil
Rated control circuit
voltage(Us)
50Hz V 110V、127V、220/230V、380/400V
50/60Hz V 75%~120%
Allowable control
circuit voltage(Us)
Operation V 20%70%
Release V
Coil power
consumption
Pull-in VA ≤300 ≤500 ≤600 ≤800
Holding VA ≤30 ≤11
Auxiliary contact
Contact specification A / 2NO/2NC
Agreed heating current(Ith) A 10
Rated operating AC V 380
voltage(Ue) SD V 220
Rated control AC-15 VA 360
capacity DC-13 W 33

Shape and Installation Dimensions

CJX2s-120–160

CJX2s-120-160

CJX2s-185-800

CJX2s-185-800

Model Amax Bmax Cmax Dmax Emax Fmax a b Φ
EXC7-185-265 124 174 167 290 197 219 96 113.5/141.5 7
EXC7-330-500 156 212 210 318 239 261 120 180/186 9
EXC7-630-800 171 231 236 333 333 288 133 180/186 9

EXC7 Accessory Selection Guide

Product Installation Diagram

EXC7 Accessory Selection Guide

Surge Suppression Module Technical Parameters

Product Appearance Product Model Delay Range(s) Delay Type Applicable Contactor Model
Surge Suppression Module Technical Parameters KTD-C1 0.1-3 On-delay EXC7-09~630
KTD-C2 0.1-30
KTD-C3 10-180
KTD-D1 0.1-3 Off-delay
KTD-D2 0.1-30
KTD-D3 10-180

Technical Parameters of Auxiliary Contact Block

Product Appearance Product Model NO(Normally Open) NC(Normally Closed) Applicable Contactor Model
Technical Parameters of Auxiliary Contact Block-1 KAT-M20 2 0 EXC7-M06~M16
KAT-M11 1 1
KAT-M02 0 2
KAT-M40 4 0
KAT-M31 3 1
KAT-M22 2 2
KAT-M13 1 3
KAT-M04 0 4
Technical Parameters of Auxiliary Contact Block-2 KAT-20 2 0 EXC7-09~630
KAT-11 1 1
KAT-02 0 2
Technical Parameters of Auxiliary Contact Block-3 KAT-40 4 0
KAT-31 3 1
KAT-22 2 2
KAT-13 1 3
KAT-04 0 4
Technical Parameters of Auxiliary Contact Block-4 KAS-20 2 2
KAS-11 1 1
KAS-02 0 2

Mechanical Linkage Matching

Product Appearance Product Model Applicable Contactor Model
Mechanical Linkage Matching-1 KMI Mechanical Chain Store EXC7-09~38
Mechanical Linkage Matching-2 KMI Electrical Chain Store EXC7-09~95

Dust Cover Matching

Product Appearance Product Model Applicable Contactor Model
Dust Cover Matching-1 KDC-1 EXC7-09~38
Dust Cover Matching-2 KDC-2 EXC7-40~95

Surge Suppression Module Technical Parameters

Product Appearance Product Model Matched Fuse Rang(A) Applicable Contactor Model
Surge Suppression Module Technical Parameters-1 FS-M AC/DC 24~48V

AC/DC 100~250V

AC/DC 380~440V

EXC7-M06~M16
Surge Suppression Module Technical Parameters-2 FS-18 EXC7-09~18
FS-32 EXC7-25~32
Surge Suppression Module Technical Parameters-3 FS-65 EXC7-40~65
FS-95 EXC7-80~95

Technical Parameters of Thermal Overload Relay

Product Appearance Rated Current(A) Matched Fuse Rang(A) Applicable Contactor Model
aM gG
JR28s-25JR28s-25 0.1~0.16 0.25 2 EXC7-09

EXC7-12

EXC7-18

EXC7-25

0.16~0.25 0.5 2
0.25~0.4 1 2
0.4~0.63 1 2
0.63~1 2 4
1~1.6 2 4
1.25~2 4 6
1.6~2.5 4 6
2.5~4 6 10
4~6 8 16
5.5~8 12 20
7~10 12 20
9~13 16 25
12~18 20 35
17~25 25 50
JR28s-36JR28s-36 23~32 40 63 EXC7-32

EXC7-38

28~36 40 80
JR28s-93JR28s-93 23~32 40 63 EXC7-40

EXC7-50

EXC7-65

EXC7-80

EXC7-95

30~40 40 100
37~50 63 100
48~65 63 100
55~70 80 125
63~80 80 125
80~93 100 160

How We Support Your Business

EXC7 OEM AC contactor customization for switchgear builders

OEM / ODM

Learn more →

Custom coils, accessory kits and branding on the full EXC7 platform, with IEC type-test documentation for switchgear certification.


Custom coils · Accessory kits · Type tests

EXC7 AC contactors wholesale supply 9A to 800A

Wholesale

Learn more →

Factory-direct pricing and mixed-frame containers for distributors covering the whole contactor category from 9A to 800A.


Factory pricing · Mixed frames · Global shipping

EXC7 distributor technical support and application engineering

Distributor Support

Learn more →

Application engineering, cross-reference lists and priority production for partners serving motor control and switchgear markets.


Application support · Cross references · Priority lead times

Ready to Standardise on the EXC7 Family?

OEM/ODM, wholesale pricing and distributor support — one enquiry gets you a factory-direct quotation across the EXC7 range from 9A to 800A, with the coils and accessories your panel needs.

Contact Our Sales Team

Frequently Asked Questions

What is the difference between the EXC7 standard and high-current series?

The standard EXC7 series covers 9A to 110A (AC-3 at 400V) with a 690V insulation class and is used for motors up to 55kW. The high-current series covers frames from 120A to 800A with 1000V insulation, a dual-coil energy-saving control circuit and standard 2NO+2NC auxiliary contacts — for large motors, incoming feeders and power switching up to 450kW.

What does AC-3 vs AC-4 mean for contactor sizing?

AC-3 is normal motor duty: starting a motor and cutting it while running. AC-4 is severe duty: inching and plugging, where the contactor opens and closes while the motor is starting or reversing, drawing up to six times rated current. A contactor sized for AC-3 must be derated for AC-4 use — the EXC7 technical tables list both current columns so you can size accordingly.

How does the dual-coil circuit save energy?

Conventional contactors hold their armature with a coil sized for the high pull-in current, wasting energy continuously. The EXC7 high-current frames energise a high-power coil only for the pull-in moment, then switch to a low-power holding coil. Holding consumption falls by over 40%, reducing heat and power cost in panels where contactors stay energised for hours.

Can the EXC7 be combined with thermal overload relays?

Yes. The EXC7 mates directly with JR28s thermal overload relays (JR28s-25 for 09-25, JR28s-36 for 32-38, JR28s-93 for 40-95), forming an electromagnetic starter with overload and phase-loss protection. For the EXQ7 assembled starter or motor-control applications, contact our sales team for matched sets.

Which auxiliary and accessory options are available?

The EXC7 family is supported by top-mounted auxiliary contact blocks (KAT, NO/NC combinations up to 4 contacts), side-mounted blocks (KAS), pneumatic time-delay heads (KTD), dust covers (KDC), surge suppression modules (FS) and mechanical/electrical interlocks (KMI) for reversing contactor pairs — all listed in the EXC7 accessory selection guide.

Name