Home > Product > All Product > HUM8PV Photovoltaic Moulded Case Circuit Breaker

HUM8PV Photovoltaic Moulded Case Circuit Breaker

The HUM8PV series is a photovoltaic molded case circuit breaker rated 16A–690A at DC 1000V. Provides overload long-time delay and short-circuit instantaneous protection. Available in 3P and 4P with multiple accessories (shunt release, auxiliary/alarm contacts, motor mechanism). Complies with IEC 60947-2. For solar PV systems, combiner boxes, and DC distribution.

Standard: IEC 60947-2

Rated Current: 16A – 690A (125/250/400/630 frame)

Rated Voltage: DC 1000V

Poles: 3P, 4P

Breaking Capacity (Icu/Ics): Up to 65kA / 50kA (DC750V)

Applications: Solar PV systems, combiner boxes, DC distribution, inverter protection

Send Inquiry

Product Information

  • Product Details
  • Downloads
  • Inquiry

1.Application

HUM8PV photovoltaic moulded case circuit breaker(hereinafter referred to as circuit breaker) isapplied to the DC circuit with rated voltage up to DC1000 V, and rated current 16A to 690A.Featured with functions of overload long time delay protection and short circuit instantaneousprotection, the product can distribute electric power,and protect the line and the equipmentfrom being damaged due to overload, short circuit, and other failures.This product accords with the standard of IEC60947-2.

2.Normal operation conditions

1.Ambient temperature:-25°C~+70°C;average temperaturewithin24h:≤+35°C
2. Altitude: $ \leqslant $ 2000m
3. Humidity: The air relative humidity under the highest temperature +40C cannot surpass 50%;Under the lowest temperature has a higher relative humidity, the wettest month’s averagelowest temperature cannot surpass +25C, and the average relative humidity cannotexceed 90%;
4.Pollution degree:class3
5. Mounted at places without explosive risk,without gases that may be corrosive to metal orgases that may cause damage to the insulation, and with little conducting dust
6.Mounting category:III

3.Model and meaningl

1.Model and meaning

Release type and accessories code

Accessories
name
No
accessories
Alarm
contact
Shunt
release
Auxiliary
contact
Shunt release
and auxiliary
contact
Two groups
of auxiliary
contacts
Shunt release
and alarm
contact
Auxiliary
contact and
alarm contact
Shunt release,
auxiliary contact
and alarm contact
Two groups
of auxiliary
contacts,
alarm contact
Over current release type        Code
Instantaneous release 200 208 210 220 240 260 218 228 248 268
Duplex release 300 308 310 320 340 360 318 328 348 368
Note:As  per  power/load  wiring  mode,E,F  type  for  3P;G,H,I  type  for  4P

Power systems for above wiring mode please check sheet 2.

To earth insulation system Negative grounding system Neutral point grounding system
DC500V E E、F
DC750V E、H F、G、I H
DC1000V H 1 H

4.Main technical parameters

Frame size rated current 125 250 400 630
Rated current In(A) 16、20、25、32、40、50、63、80、100、125 100、125、160、180、200、225、250 225、250、315、350、400 400、500、630
Pole number 3 4 3 4 3 4 3 4
Rated insulation voltage Ui(V) 1000
Rated impulse withstand voltage Uimp(V) 8000
Rated working voltage Ue(V) DC 500
DC750
DC750
DC 1000
DC 500
DC750
DC750
DC 1000
DC 500
DC750
DC750
DC 1000
DC 500
DC750
DC750
DC 1000
Using category A
Rated limit/service
short circuit
breaking capacity
Icu/lcs(kA)
DC500 15/15 65/65 65/65 65/65
DC750 5/5 15/15 40/20 50/50 40/20 50/50 40/20 50/50
DC1000 5/5 40/20 40/20 40/20
Flashover distance(mm) ≤50 ≤50 ≤100 ≤100
Operation
performance
(times)
Energized 5000 5000 1000 1000
Non-energized 10000 10000 5000 5000

5.Protection characteristics curve

1.HUM8PV-125 current temperature protection characteristics curve

2.HUM8PV-250 current temperature protection characteristics curve

3.HUM8PV-400 current temperature protection characteristics curve

4.HUM8PV-690 current temperature protection characteristics curve

5. The temperature reducing capacity coefficient at different temperature.

10℃ 20℃ 30℃ 40℃ 50℃ 60℃ 70℃
HUM8PV-125 1.15In 1.11In 1.15In 1In 0.93In 0.85In 0.8In
HUM8PV-250 1.15In 1.11In 1.15In 1In 0.93In 0.85In 0.79In
HUM8PV-400 1.16ln 1.11In 1.15In 1In 0.94In 0.86ln 0.81In
HUM8PV-630 1.17In 1.11In 1.15In 1In 0.9In 0.8In 0.7In

6.The reducing capacity coeficient in high altitude:when the altitude exceeds 2000m,the circuit breaker should be adjusted as sheet4

Altitude(m) 2000 3000 4000 5000
Power frequency withstand voltage 3000 2500 2000 1800
Working current adjustment coefficient 1 0.94 0.88 0.83

7.DC system application: the following aspects should be considered before choose breaker in DC system.

a.rated operation voltage, considering cascaded pole number

b.rated current, considering load power

c. breaking capacity, considering maximum short circuit current at mounting site

d. Grounding system mode, see sheet 5

System type Grounding system Ungrounding system
All kinds of fault types
Failure effect Failure l Generate maximum short circuit current
Contact connecting to positive pole break
U/2 voltage produce maximum short circuit current
Contact connecting to negative pole break
No effect
Failure ll Generate maximum short circuit current
All the cascaded contacts break
Generate maximum short circuit current
All the cascaded contacts break
Generate maximum short circuit current
All the cascaded contacts break
Failure I No effect                Same as failure l
But only for contact connecting to negative pole
No effect
The worst situation Failure l Failure l and Failure ll Failure ll
Breaking situation Cascade in positive pole and break together For each pole,break maximum short circuit current when U/2 Two poles break together

6.Overall and mounting size

1.E type wiring for 3PHUM8PV-125(front connection)

2.H type wiring for 4P HUM8PV-125(front connection)

3.E type wiring for 3P HUM8PV-250(front connection)

4.H type wiring for 4PHUM8PV-250(front connection)

5.E type wiring for 3PHUM8PV-400(front connection)

6.H type wiring for 4P HUM8PV-400 (front connection)

7.E type wiring for 3PHUM8PV-630(front connection)

8.H type wiring for 4P HUM8PV-630(front connection)

7.Accessories

1.Accessories can be provided as per user’s requirement.

2.Shunt release parameters:

Rated voltage Us:AC230V,400V;DC 220-250V,24-30V

Breaker can reliably break at(70%-110%)Us, and action time is 10ms-30ms.

Note:when uses DC24V-30V shunt release, the maximum length of copper line should meet the requirements of sheet 6

Rated control power voltage Us
(DC24V~30V)
Input power Maximum length of copper line
1.5mm² 2.5mm²
100%Us 50W 150m 250m
85%Us 50W 100m 160m

3. Rated value of auxiliary contact and alarm contact:

Conventional thermal current Ith=3A;rated working current le=0.79A(AC230V); le=0.47A(AC400V); le=0.15A(DC250V)

4. Parameters of motor operation mechanism see sheet7, total height of motor operation mechanism see sheet 8. The following isthe wiring diagram of motor operation mechanism

Frame size rated current le(A) Rated working voltage Ue(V) Starting current(A) Action time(s) Rated operation frequency(times/h) Mechanical life (times)
125 AC 110V~230V
50Hz
DC 110V~220V
≤0.5 ≤0.8 180 9000
250
400 ≤2 120 5000
630 3000

The power capacity of motor operation mechanism should be large enough to ensure the voltage impacted on at starting current should be no less than 85%Ue

Model HUM8PV-125 HUM8PV-250 HUM8PV-400 HUM8PV-630
Height 170 199 230 246

Wiring diagram of motor operation mechanism

5. Mounting size of rotating handle operation mechanism see sheet 9

Model HUM8PV-125 HUM8PV-250 HUM8PV-400 HUM8PV-630
Mounting size(H) 54 54 76 83

Overall and mounting hole drawing of A type(square)handle

Model and specification A1 A2
D 中42 φ 63
d 中4.5 φ5.5
a 65 88
b 65 88
L 60 140

Overall and mounting hole drawing of B type(round)handle

Model and specification B1 B2 B3
D φ33 φ33 中33
d 中4.5 φ4.5 中4.5
a φ 53 φ53 φ53
L 65 125 95

Overall and mounting sizes of centralized rotating handle operation mechanism

8.Installation and maintenance

1.Matters need attention before installation:
a.Appearance shall be well and no-loaded action normal; rated value of breaker and accessories should conform to working conditions at mounting site;no obvious shock at mounting site and conform to normal working conditions
b. Insulation test should be taken before ex-factory. Use 1000VDCMo meter to do retest before installation, among poles of circuit breaker,the insulating resistance between the same pole entering and outlet terminal should be no less than 20MΩ at breaking state
2.Cross section area of conductors should exceed the size regulated in sheet10,and the connection bolt should be screwed up.
3.Characteristic of breaker and accessories should meet our order requirements.
4.The breaker handle can turn to“on”,“off”,“trip”position, when it’s “trip”,the handle rotated to “off” direction,then it can do“on”operation.
5.Before add the internal accessories, the breaker tripper should be switch off.

Rated current(A) 10 16、20 25 32 40、50 63 80 100 125 160 180、200、225 250 315、350 400
Line cross section area 1.5 2.5 4 6 10 16 25 35 50 70 95 120 185 240
Rated current
(A)
Cable cross section area Copper bar size
Quantity Cross section area(mm²) Quantity Size(mm×mm)
500 2 150 2 30×5
630 2 185 2 40×5

9.Ordering information

1.Product name and model

2. Rated current, release type,instantaneous release setting current multiple

3.Accessories name and specification

FAQ

What is a moulded case circuit breaker?

A moulded case circuit breaker (MCCB) is a protective device enclosed in a moulded housing. It provides overcurrent and short-circuit protection for electrical circuits, with adjustable trip settings and higher breaking capacities than miniature circuit breakers.

What is a photovoltaic circuit breaker?

A photovoltaic circuit breaker is specifically designed for DC solar applications. It handles the unique characteristics of PV systems — higher DC voltages (up to 1000V or 1500V DC), non-zero-crossing DC arc extinction, and continuous load variations from solar irradiance.

What is the difference between a circuit breaker and a molded case breaker?

A “circuit breaker” is a general term for any automatic overcurrent protection device. A “molded case circuit breaker” (MCCB) is a specific type — housed in a moulded insulating casing, with higher current ratings (up to several thousand amps), adjustable trip settings, and higher breaking capacities than miniature circuit breakers (MCBs).

Which is better, ACB or MCCB?

Neither is universally “better” — they serve different applications. ACB (Air Circuit Breaker) is used for low-voltage main distribution (high current, up to 6300A), with adjustable protection and high breaking capacity. MCCB (Moulded Case Circuit Breaker) is used for branch circuit protection (up to 1600A), more compact and cost-effective for feeder circuits. Choose based on application current rating and protection requirements.