Home > Product > All Product > EXC7-M Miniature AC Contactor

EXC7-M Miniature AC Contactor

Full-Size Performance in 40% Less Space — 6-16A, 3P/4P

The EXC7-M is a miniature AC contactor that shrinks a 6-16A motor-switching contactor into a footprint more than 40% smaller than mainstream equivalents, with the standard 1NO+1NC auxiliary contact already included. Offered in 3P and 4P versions with AC coils, plus DC coil (Z), PCB pin (P) and tool-free slide-lock (N) derivatives for confined control panels and OEM assemblies.

Model

✓
EXC7-M Series — Miniature AC ContactorEXC7-M06 · EXC7-M09 · EXC7-M12 · EXC7-M16 (+Z / +P / +N variants)

Request a Wholesale Quotation

IEC 60947-4-1 · CE approved · 1NO+1NC standard · 690V insulation

40% Smaller Footprint
1NO+1NC Standard
Rail & Screw Mount

Product Details

  • 6-16A AC-3 miniature AC contactor switching motors to 7.5kW at 380/400V; 3P or 4P.
  • Body over 40% smaller than mainstream equivalents — saves space in tight control panels.
  • Standard 1NO+1NC auxiliary contacts; AC coils plus DC (Z), PCB pin (P) and tool-free slide-lock (N) derivatives.
  • Ui 690V; IP20; ambient -35°C to +70°C; IEC 60947-4-1; CE approved.
Send Inquiry

Product Information

  • Product Details
  • Downloads
  • Inquiry

Three Key Features

  • Smaller footprint, ideal for installa on in ght spaces
  • Boas ng superior cost-eƆectiveness, this product is priced lower than other products of the same current ra ng
  • Deriva ve DC and pin-type variants are available to adapt to diƆerent working scenarios

Product Structural Analysis Diagram

EXC7-M Product Structural Analysis Diagram

Product Overview

The EXC7-M Series AC Contactors feature an innovative appearance and a compact structure, and are suitable for occasions involving frequent staDžing, control of AC motors, and remote circuit breaking. When used in combination with thermal relays, they form electromagnetic staDžers. Implementation Standards: IEC 60947-1, IEC 60947-4-1.

Main Technical Parameters

  • Rated working current: 6-16A;
  • Rated working voltage: 220V to 690V;
  • Rated insulation voltage: 690V;
  • Polarities: 3P, 4P
  • Installation method: rail and screw

Working Conditions and Installation Conditions

Category Working conditions and installation conditions
Installation type Ⅲ
Pollution degree 3
Certification mark CE
Enclosure protection rating IP20(excluding terminals)
Ambient air temperature The maximum operating temperature is-35℃to+70℃,and the normal operating temperature is

-5℃ to +40℃The average value within 24 hours does not exceed+35℃.

If used outside the normal operating temperature range,for details,please refer to the “Instructions for

Use in Abnormal Environments”

Altitude No more than 2000m
Ambient air temperature When the maximum temperature is+70℃,the relative humidity of the air shall not exceed 50%.

Higher relative humidity is allowed at lower temperatures For example,it reaches 90%at+20℃.
Special measures should be taken for condensation that occasionally occurs due to changes in humidity

Installation conditions The inclination between the installation surface and the vertical surface shall not exceed+5°
Shock and vibration The product should be installed and used in a place free from significant shaking,shock and vibration

Instructions for Use in Extreme Temperature Environments

  • The GB/T 14048.1 standard speciƍes the normal operating ambient temperature for the product. When used within this normal range,the product’s peƐormance is not signiƍcantly aƆected.
  • When the operating ambient temperature exceeds +40°C, it is necessaƔ to consider derating the permissible temperature rise limits.In such cases, the rated operating current must be reduced, and the number of contactors installed in standard assemblies must be decreased. Failure to do so may result in product damage, a shoƑened seƒice life, reduced operational reliability, and an impact on the product’s operating range. When the operating ambient temperature falls below -5°C, consideration must be given to the fact that greases used for insulation and lubrication may solidify at low temperatures, potentially causing product failure. Therefore, manufacturers and users should consult each other regarding design or usage requirements.
  • The table below lists the rated operating current correction factors for instances where the rated operating voltage remains constant but the operating ambient temperature exceeds 55°C.
Ambient temperature(℃) 55 60 65 70
Correction Factor 1 0.93 0.875 0.75
  • The following table provides correction factors for the rated impulse withstand voltage and rated working current when the altitude exceeds 200Om with the rated working voltage unchanged:
Altitude(m) 2000 3000 4000 5000
Correction Factor for Rated Impulse Withstand Voltage 1 0.88 0.78 0.7
Correction Factor for Rated Working Current 1 0.92 0.9 0.85

Features and Performance

Main Technical Parameters
Model EXC7-M06 EXC7-M09 EXC7-M12 EXC7-M16
Main circuit characteristics
Polar number 3P/4P
Rated insulation voltage(Ui) V 690
Rated operating voltage(Ue) V 380/400,660/690
Agreed heating current(Ith),AC-1 rated operating current 20
Rated working
current (le)
AC-3,380/400V A 6 9 12 16
AC-3,660/690V A 3.8 4.9 4.9 4.9
AC-4,380/400V A 6 9 9 12
AC-4,660/690V A 3.8 4.9 4.9 4.9
Rated working
power(Pe)
AC-3,380/400V kW 2.2 4 5.5 7.5
AC-3,660/690V kW 3 4 4 4
Mechanical life 1200
Electrical life AC-3 10,000 times 120
AC-4 22
Operating

frequency

AC-3 Times per hour 1200
AC-4 300
The wiring capability of the main circuit terminals
Flexible wire

With terminal blocks

1 wire mm² 1..2.5
2 wires mm² 1…1.5
Hard wire

No terminal blocks

1 wire mm² 1..2.5
2 wires mm² 1..2.5
Fastening torque N.m 0.8
Coil
Rated control
circuit voltage
(Us)
50Hz V 243648110127220380415
50/60Hz V 243648110127220380415
DC V 12243648110127220
Allowable control
circuit voltage(Us)
Operation V AC:75%~120%;DC:80%-120%
Release V AC:20%~65%;DC:10%-70%
Coil power

consumption

Pull-in VA 20-40(≤4.5W DC)
Holding VA 9.0(≤4.5W DC)
Auxiliary contact
Contact specification A 1NO/1NC
Agreed heating current(Ith) A 10
Rated operating AC V 380/400
voltage(Ue) SD V 220
Rated control AC-15 VA 360
capacity DC-13 W 33

Outline and Mounting Dimensions

EXC7-M06~M16

EXC7-M06~M16

Model Amax Bmax Cmax Dmax a b Φ
EXC7-M06-M16 45.5 59 58 94 35±0.35 50±0.48 4.2
EXC7-M06Z-M16Z 45.5 59 70 106 35±0.35 50±0.48 4.2
EXC7-MP06-MP16 45.5 59 66 102 / / /

EXC7-M06N~M16N

EXC7-M06N~M16N

EXC7-M06~M16+JR28s–M

EXC7-M06~M16+JR28s-M

How We Support Your Business

EXC7-M OEM customization of miniature contactors

OEM / ODM

Learn more →

Custom coils, DC derivatives and branding built on the compact EXC7-M platform, with full IEC test documentation.


Custom coils · DC variants · IEC reports

EXC7-M miniature contactors wholesale supply

Wholesale

Learn more →

Factory-direct pricing for distributors serving panel builders, HVAC and OEM control markets with the full 6-16A range.


Factory pricing · Flexible MOQ · Global shipping

EXC7-M distributor support and technical selection help

Distributor Support

Learn more →

Selection guides, cross-reference support and priority production for partners building the compact contactor category.


Account manager · Cross references · Priority lead times

Ready to Stock the EXC7-M Series?

OEM/ODM, wholesale pricing and distributor support — one enquiry gets you a factory-direct quotation for EXC7-M miniature AC contactors in AC, DC, pin and slide-lock versions.

Contact Our Sales Team

Frequently Asked Questions

What is a miniature AC contactor?

A miniature AC contactor is a compact-sized contactor for switching small three-phase and single-phase loads — typically motors up to 7.5kW at 400V — where panel space is limited. The EXC7-M covers 6-16A at AC-3 with a body over 40% smaller than mainstream equivalents, making it a space-saving alternative for machine control and small distribution panels.

What is the difference between EXC7-M, EXC7-MZ and EXC7-MP?

EXC7-M is the standard AC-coil version. EXC7-MZ adds a Z suffix for DC coils (12-220V), for control systems with DC outputs. EXC7-MP is the pin-type version whose terminals solder directly to a PCB, used in assembled control modules. All share the same 45.5mm body width and 6-16A switching capacity.

How many auxiliary contacts does the EXC7-M include?

The EXC7-M comes standard with one normally open and one normally closed auxiliary contact (1NO+1NC), rated 10A thermal current with AC-15 360VA / DC-13 33W control capacity. This covers status feedback to a PLC or interlocking in most small applications without an extra auxiliary block.

Can a 4P EXC7-M switch a single-phase load with neutral?

Yes — that is the main use of the 4P version. Three poles switch the three phases (or the live lines of a three-pole single-phase group) while the fourth pole switches the neutral, giving full isolation of the controlled circuit. For a pure three-phase motor, the 3P version is sufficient.

What is the working temperature range and enclosure rating?

The EXC7-M operates from -35°C to +70°C maximum (-5°C to +40°C normal), at altitudes up to 2000m, with an IP20 enclosure excluding terminals. The optional transparent dust cover adds protection against airborne dust in harsh machine rooms.