8 ms Transfer in a DIN Rail Frame — ATS for Grid, Generator and PV Backup

The EXT3PB-160 is a PC class automatic transfer switch that moves the load between two supplies in 8 ms, fast enough to carry household electronics and small drives through a mains outage. It mounts on 35mm DIN rail as a two-station unit with an integrated controller, and accepts grid-to-grid, grid-to-generator and inverter-to-grid arrangements with self-restoring return.

Model

✓
EXT3PB-160 Series — PC Class Automatic Transfer SwitchEXT3PB-160 2P / 4P · Ie 16-160A · AC 400V · transfer time 8 ms

Request a Wholesale Quotation

IEC 60947-6-1 / GB/T 14048.11 · PC class AC-33iB · 50kA short-circuit withstand · 8kV Uimp

8 ms Transfer
16-160A Range
DIN Rail 2P/4P

 

 

Send Inquiry

Product Information

  • Product Details
  • Downloads
  • Inquiry

Product Introduction

Control Device: Built-in Controller

Product Structure: No power interruption, rail-mounted, high current capacity, compact size, two-section design, simple structure, integrated ATS.

Features: Fast switching speed, low failure rate, easy maintenance, and reliable performance.

Wiring Method: Front panel wiring

Transfer Modes: Grid-to-grid, grid-to-generator, solar-to-grid, and automatic transfer with self-restoring function.

Frame Size: 160

Rated Current (A): 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160

Product Type: Direct load type

Number of Poles: 2P, 4P

Product Standard: GB/T 14048.11

ATS Class: PC Class

Transfer Time: 0.008s / 8ms

Product Overview

The Dual Power Automatic Transfer Switch (ATS) is a newly developed compact power transfer switch designed for household applications. It is mainly used to monitor whether the main power supply or backup power supply is operating normally. When the main power supply fails, the backup power supply automatically starts operating to ensure continuity, reliability, and safety of the power supply. This product is specially designed for household DIN rail installation.

The Dual Power Automatic Transfer Switch is suitable for emergency power supply systems operating at 50Hz or 60Hz with a rated AC voltage of 400V. The ATS features a robust structure, reliable switching performance, easy installation and maintenance, and a long service life. It is widely used in applications where continuous power supply is required. It supports both automatic and manual operation. The ATS consists of a transfer switching device (TSE) and a controller.

In accordance with GB/T 14048.11, which is based on IEC 60947-6-1 (Low-voltage Switchgear and Controlgear – Part 6-1: Multiple Function Equipment – Transfer Switching Equipment), the ATS is designed to meet the requirements for low-voltage switching and control equipment.

Normal Operating and Installation Conditions

1.Ambient Air Temperature

The maximum ambient temperature shall not exceed +40°C, and the minimum temperature shall not be lower than -5°C. The average temperature within 24 hours shall not exceed +35°C.

2.Altitude

The altitude of the installation site shall not exceed 2,000 meters above sea level.

3. Atmospheric Conditions

When the maximum ambient temperature reaches +40°C, the relative humidity at the installation site shall not exceed 50%. Higher relative humidity is permitted at lower temperatures. For example, at +25°C, the relative humidity may reach 90%. Special measures should be taken to prevent condensation on the product surface caused by temperature variations.

4. Pollution Degree

The ATS complies with Pollution Degree 3 as specified in GB/T 14048.11.

5. Installation Category

The installation category of the ATS shall comply with the category specified in GB/T 14048.11.

6. Installation Conditions

The ATS can be installed vertically in a control cabinet or distribution panel. Ensure that the installation clearances meet the requirements specified in Figure 5.

Technical Specifications

Parameter Specification
Frame Size 160A
Rated Current (le) 16,20,25,32,40,50,63,80,100,125,160A
Rated Insulation Voltage(Ui) AC 690V,50Hz
Rated Operational Voltage(Ue) AC400V,50Hz
Classification PC Class:Capable of making and carrying current,
but not intended for breaking short-circuit current
Utilization Category AC-33iB AC-31B
Number of Poles 2P 4P
Weight 1.7 2.6
Electrical and Mechanical Endurance Lifespan:1,300 operations;manual operations:4,000
Rated Short-Circuit Current(Iq) 50kA
Short-Circuit Protective Device(Fuse) RT16-250A
Rated Impulse Withstand Voltage(Uimp) 8kV
Control Circuit Rated control voltage(Us):AC 220V/50Hz;normal operating range:85-110%of Us
Auxiliary Circuit 1 relay,each equipped with two sets of changeover contacts;contact capacity:AC 220V/50Hz,le=5A
Contactor Transfer Time <50ms
Operating Transfer Time <50ms
Return Transfer Time <50ms
Power Supply Disconnection Time <50ms

160 Wiring Diagram

EXT3PB-160 ATS PC 160 Wiring Diagram

External and Mounting Dimensions

EXT3PB-160 ATS PC External and Mounting Dimensions

EXT3PB-160 ATS PC External and Mounting Dimensions-1 EXT3PB-160 ATS PC External and Mounting Dimensions-2

 

 

 

 

Name
Size
Release time
Operate